🔹 Product Overview
The ABB 3BSE005023R1 CI626A is a standalone Bus Administrator interface used in ABB Advant Fieldbus 100 (AF 100) communication systems. Its primary role is to provide bus administration and control communication traffic on an AF 100 network.
The CI626A is specifically associated with coaxial AF 100 bus connections and includes an integrated modem. It can be used where an AF 100 network requires a dedicated bus administrator rather than relying on another communication interface with bus-master capability.
This module is particularly relevant for maintenance, replacement, and lifecycle support of legacy ABB Advant and ACS 600-based automation installations.
⚙️ Key Features
- ABB CI626A standalone Bus Administrator
- ABB part number 3BSE005023R1
- Designed for Advant Fieldbus 100 communication
- Supports bus administration and master functions
- Coaxial AF 100 network interface
- Integrated communication modem
- Suitable for legacy ABB automation and drive-system installations
- Useful as a replacement spare for existing CI626A installations
- Revision and connector configuration should be verified before replacement
🔌 Communication & System Integration
The CI626A operates as an active bus administrator on the AF 100 network. ABB documentation identifies CI626A and CI627A as standalone bus administrators, with CI626A using coaxial connectors and CI627A using twisted-pair screw connectors.
In a typical installation, the CI626A coordinates communication activity on the AF 100 network while connected stations exchange process and control information through their respective communication interfaces.
When replacing a CI626A, the existing network topology, station configuration, cable type, connector arrangement, and module revision should be checked carefully.
🏭 Typical Applications
The CI626A can be encountered in:
- ABB Advant automation systems
- ABB Advant Controller installations
- ABB AF 100 Fieldbus networks
- ABB ACS 600 MultiDrive systems
- Legacy distributed control installations
- Industrial drive communication networks
- Process automation and manufacturing systems
- Replacement and maintenance of discontinued ABB control hardware
📋 Technical Datasheet
| Parameter | Specification |
|---|---|
| Brand | ABB |
| Model | CI626A |
| Product Series | Advant Fieldbus 100 / AF 100 |
| Product Name | Bus Administrator Board |
| Product Type | Standalone Bus Administrator Interface |
| Part Number | 3BSE005023R1 |
| Communication Bus | Advant Fieldbus 100 |
| Network Interface | Coaxial AF 100 |
| Communication Function | Bus Administration / Bus Master |
| Installation | Industrial Automation / Control System |
🛠️ Installation & Commissioning
Before installation, isolate the relevant control-system power and follow the plant’s electrical safety procedures.
Verify that the replacement unit has the same CI626A designation and 3BSE005023R1 part number as the existing module. Connector type and revision should also be compared.
During commissioning:
- Inspect the module and connectors for physical damage.
- Verify AF 100 cable routing and termination.
- Confirm the network topology before powering the system.
- Check station addressing and bus configuration.
- Power the system according to the applicable ABB procedure.
- Monitor communication status and diagnostic indications.
- Confirm stable communication with the connected AF 100 stations.
🔍 Troubleshooting
No AF 100 communication:
Check the coaxial network connections, termination, station configuration, and bus administrator status.
Intermittent communication:
Inspect coaxial cables, connectors, shielding, and termination points. Loose or damaged connections can cause unstable fieldbus communication.
Module does not assume bus administration:
Check whether another device is configured as the active bus master and verify the AF 100 network configuration.
Communication faults after replacement:
Compare the replacement module’s part number and revision with the original unit. Do not assume that visually similar ABB communication boards are interchangeable.
🔧 Maintenance Recommendations
Keep the CI626A in a clean, dry control cabinet and protect it from excessive dust, moisture, vibration, and electrical interference.
For legacy systems, it is advisable to maintain a tested spare because a failure of the bus-administration function can affect communication across multiple connected stations.
When removing a replacement board from service inventory, record its part number, revision, installation location, and test status to simplify future maintenance.
🔄 Replacement Considerations
The 3BSE005023R1 CI626A should be matched by exact part number and compatible revision whenever possible.
Do not automatically substitute a CI627A merely because it also performs standalone bus-administrator functions. ABB identifies the CI627A as the twisted-pair version, while CI626A uses coaxial AF 100 connections.
For a replacement project, verify:
- Exact ABB part number
- CI626A designation
- Hardware revision
- AF 100 media type
- Connector arrangement
- Existing bus topology
- System configuration
- Firmware or communication requirements
❓ FAQ
What is ABB CI626A 3BSE005023R1?
It is a standalone Bus Administrator interface for ABB Advant Fieldbus 100 networks.
What is the main function of the CI626A?
Its main function is to administer and control communication activity on an AF 100 network.
Is CI626A the same as CI627A?
No. Both are standalone AF 100 bus administrators, but CI626A is designed for coaxial AF 100 connections while CI627A uses twisted-pair screw connections.
Is 3BSE005023R1 the ABB part number?
Yes. 3BSE005023R1 is the ordering/part number associated with CI626A.
Can CI626A be used as a general Ethernet communication module?
No. It is an AF 100 bus-administrator interface and should not be treated as a general-purpose Ethernet communication board.
What should be checked before replacing a CI626A?
Check the exact part number, hardware revision, AF 100 media, connectors, network configuration, and system architecture.
Is CI626A suitable for legacy ABB systems?
Yes. It is particularly useful for maintenance and spare-part replacement in legacy ABB Advant/AF 100 installations.
Can CI626A and CI627A be directly interchanged?
They should not be considered directly interchangeable without verifying the network media and system configuration.
📦 10 Related ABB Models / Components
- ABB CI627A
- ABB CI626
- ABB CI627
- ABB CI520
- ABB CI522
- ABB CI526
- ABB CI527
- ABB CI630
- ABB CI631
- ABB NDBU-85
✅ Product Summary
The ABB 3BSE005023R1 CI626A is a dedicated AF 100 Bus Administrator interface designed for legacy ABB automation and drive communication systems. Its standalone bus-master function and coaxial AF 100 interface make it an important spare for installations where continued operation of an existing Advant Fieldbus 100 network is required.
For replacement projects, always match the exact CI626A / 3BSE005023R1 designation and verify the network media, hardware revision, and system configuration before installation.