π Product Introduction
The DEIF RMC-111D is a current protection relay designed primarily for short-circuit protection in generator and electrical power systems.
It monitors three-phase currents and detects excessive short-circuit current conditions. When the measured current exceeds the preset threshold, the relay initiates a time-controlled trip signal to help protect generators and connected electrical equipment.
The RMC-111D features adjustable short-circuit current settings, LED status indication, and one relay output contact. It is suitable for marine and land-based power installations, generator protection systems, and industrial electrical control applications.
βοΈ Technical Specifications
- Brand: DEIF
- Model: RMC-111D
- Product Type: Current / Short Circuit Protection Relay
- Protection Function: Short-Circuit Protection (I>>)
- ANSI Protection Code: 50
- Current Measurement: Three-Phase
- Short-Circuit Setting Range: 100β400% of Rated Current (In)
- Measuring Range: 0.3β5.0 A AC
- Response Time: Less Than 50 ms
- Relay Output: 1 Changeover Contact
β Key Features
- Dedicated short-circuit current protection
- Three-phase current monitoring
- Adjustable short-circuit current threshold
- Adjustable time delay
- LED indication for fault and relay activation
- One changeover relay contact
- DIN rail or base mounting
- Designed for generator and electrical system protection
- Suitable for marine and land-based installations
π§ Additional Technical Information
- Frequency Range: 40β70 Hz
- Maximum Continuous Input Current: 4 Γ In
- Input Current Capacity: 20 Γ In for 10 seconds, maximum 75 A
- Short-Time Input Current: 80 Γ In for 1 second, maximum 300 A
- Maximum Measuring Load: 0.3 VA per phase
- Contact Rating: 8 A at 250 VAC / 24 VDC
- Maximum Contact Voltage: 250 VAC / 150 VDC
- Operating Temperature: -25 to +70Β°C
- Case Protection: IP40
- Terminal Protection: IP20
- Galvanic Isolation: 3250 V, 50 Hz, 1 minute
Important: The RMC-111D is available with different measuring and auxiliary supply voltage configurations. Check the exact product label and wiring diagram before installation.
β Frequently Asked Questions
Q1: What is the main function of the DEIF RMC-111D?
A: It provides short-circuit current protection for generators and electrical power systems.
Q2: Does the RMC-111D support three-phase current monitoring?
A: Yes. It measures three-phase currents and responds to the highest measured phase current.
Q3: What is the short-circuit setting range?
A: The short-circuit current threshold is adjustable from 100% to 400% of the rated current.
Q4: How many relay contacts does it have?
A: The RMC-111D has one changeover relay contact.
Q5: Can it be used in marine applications?
A: Yes. The DEIF RMC relay series is designed for both marine and land-based installations.
Q6: What should be checked before replacement?
A: Verify the measuring current range, auxiliary supply voltage, contact configuration, wiring, and mounting arrangement.
π·οΈ Related DEIF Protection Relay Models
- DEIF RMC-111D β Short Circuit Relay
- DEIF RMC-121D β Short Circuit Relay
- DEIF RMC-122D β Short Circuit and Overcurrent Relay
- DEIF RMC-131D β Differential Current Relay
- DEIF RMC-132D β Dual Overcurrent Relay
- DEIF RMC-142D β Earth Current Relay
- DEIF RMF-112D β Frequency Relay
- DEIF RMP-111D β Power Protection Relay
- DEIF RMP-112D β Power Protection Relay
- DEIF RMP-121D β Power Protection Relay
- DEIF RMQ-111D β Loss of Excitation Relay
- DEIF RMQ-121D β Loss of Excitation Relay
- DEIF RMV-112D β Voltage Relay
- DEIF RMV-122D β Voltage Relay
- DEIF RMV-132D β Voltage Relay