Product Description
The Autronica BS-100 DYFI is an analogue addressable fire detection and alarm control panel designed for medium and large fire protection installations. It monitors connected detector loops, processes alarm and pre-alarm conditions, identifies the location of activated detectors, and controls connected alarm and auxiliary equipment.
The BS-100 supports two standard detector loops, expandable to as many as 16 loops with additional BSD-100 modules. Its DYFI (Dynamic Filter Process) technology is designed to distinguish genuine fire conditions from certain non-fire phenomena, helping reduce unwanted alarms.
The panel is suitable for legacy fire detection installations in marine, industrial, and commercial facilities. Before purchasing or installing a replacement unit, verify the panel hardware revision, software version, loop configuration, and connected peripheral equipment.
Product Datasheet & Parameters
- Brand: Autronica
- Model: BS-100
- Product Series: BS-100 DYFI Fire Detection System
- Product Name: Analogue Addressable Fire Alarm Control Panel
- System Type: Analogue addressable fire detection
- Standard Detector Loops: 2
- Maximum Detector Loops: 16 with additional BSD-100 modules
- Power Supply: 230 V AC, +10% / -15%
- Battery Backup: 2 × 12 V batteries, 24 V DC total; batteries not included
- Normal Current Consumption: Approximately 170 mA under the specified unloaded condition
- Alarm Current Consumption: Approximately 370 mA under the specified unloaded condition
- Protection Rating: IP43
- Operating Temperature: -5 to +40 °C
- Enclosure: Steel cabinet with Lexan front door
- Dimensions: Cabinet dimensions vary by system configuration
- Weight: Depends on cabinet and installed modules
- Place of Manufacture: Norway (manufacturer location; confirm individual unit origin)
- Product Status: Legacy product; confirm actual condition
- Power Requirements: 230 V AC input with 24 V DC battery backup
- Discontinued: Superseded by newer Autronica fire detection systems
Main Features & Applications
- Analogue addressable detector loop monitoring
- Identification of alarm locations by loop and detector address
- Fire, prewarning, fault, and system-disablement indications
- Configurable sounder and remote alarm outputs
- Auxiliary control outputs for external equipment
- Expandable detector-loop and output configurations
- Optional communication through compatible BSL-100 modules
- Suitable for legacy marine, industrial, and commercial fire detection systems
Installation & Commissioning
- Confirm that the BS-100 panel revision and software configuration match the existing fire detection installation.
- Inspect the cabinet, internal circuit boards, terminals, connectors, and grounding points before installation.
- Verify the incoming 230 V AC supply and the specified 24 V DC battery arrangement.
- Check detector-loop wiring, polarity, cable condition, termination, and connected device compatibility.
- Confirm that optional BSD-100, BSB-100, BSJ-100, or BSL-100 modules are correctly installed where applicable.
- Load or verify the correct system configuration, detector addresses, zone descriptions, and output assignments.
- Conduct supervised tests of detectors, sounders, remote alarm signals, fault monitoring, and auxiliary outputs.
- Complete the required commissioning and acceptance tests before returning the fire protection system to service.
Installation and commissioning should be performed by qualified fire-alarm technicians using the correct Autronica documentation and site-specific configuration.
Daily Maintenance
- Check that the MAINS indicator shows normal power status.
- Review the display for fire alarms, prewarnings, faults, and disabled functions.
- Investigate any fault indication instead of repeatedly resetting the panel.
- Inspect the cabinet and accessible wiring for moisture, corrosion, loose connections, or physical damage.
- Verify battery condition and backup performance according to the maintenance schedule.
- Test detectors, sounders, and remote signalling circuits at the intervals required by the applicable fire safety standards.
- Keep a maintenance record of alarms, faults, inspections, and corrective work.
Troubleshooting & Frequently Asked Questions
Q1: What does the BS-100 panel do?
A: It monitors analogue addressable fire detector loops, displays alarm locations, and controls connected alarm and auxiliary circuits.
Q2: How many detector loops does the standard panel support?
A: Two loops are standard. The system can be expanded to a maximum of 16 loops using additional BSD-100 modules.
Q3: What does the FAULT indicator mean?
A: It indicates a detected system or circuit fault. Check the display message, affected loop, field wiring, power supply, and connected devices.
Q4: Can the BS-100 operate without backup batteries?
A: The specified system includes a 24 V battery arrangement. Battery installation and backup testing should follow the manufacturer’s instructions and applicable safety requirements.
Q5: Can a BS-100 replace another Autronica panel directly?
A: Not necessarily. Confirm the detector protocol, software version, loop configuration, peripheral modules, and programmed site data before considering a replacement.
Q6: Is the BS-100 a current-generation fire alarm panel?
A: It is a legacy product family. Autronica identifies newer systems as successors, so long-term maintenance and spare-parts availability should be evaluated.
Safety Precautions
- Fire detection and alarm systems are life-safety equipment. Do not leave protected areas without an approved alternative protection arrangement while the system is isolated.
- Isolate electrical power before carrying out internal wiring or module replacement.
- Do not connect incompatible detectors or peripheral modules.
- Never disable alarm outputs or detector loops without authorization and documented safety controls.
- Test the complete system after maintenance or component replacement.
Recommended Autronica Models & Related Products
The following are related Autronica system components and product families. They are not all direct replacements for the BS-100.
- Autronica BSD-100 – Detector Loop Expansion Module
- Autronica BSB-100 – Alarm Output Expansion Module
- Autronica BSL-100 – Communication / Data Output Module
- Autronica BSJ-100 – Control Output Module
- Autronica BSJ-101 – Control Output Module
- Autronica BS-60 – Fire Alarm Control Panel
- Autronica BU-100 – Firefighter’s Panel
- Autronica BU-101 – Marine Firefighter’s Panel
- Autronica BU-70 – Indication Panel
- Autronica BZ-32 – Zener Barrier Unit
- Autronica KDL-26B – Communication Line Splitter
- Autronica EA-2A – Microcomputer Interface
- Autronica EA-3A – Microcomputer Interface
- Autronica AutroMaster 300 – Alarm Presentation System
- Autronica AutroMaster 5000 – Alarm Presentation System