⚙️ Product Introduction
The Woodward 9907-028 Rev F SPM-A Synchronizer is an automatic generator synchronization device designed for power generation and industrial electrical control systems.
It monitors the frequency and phase relationship between an incoming generator and an energized bus, helping achieve synchronized conditions before circuit breaker closure.
The SPM-A series is designed to work with compatible Woodward 2301, 2301A, EPG, and 2500 load-sharing control systems. It provides speed-bias signals to the governor and supports automatic breaker closing when synchronization conditions are satisfied.
The 9907-028 is particularly suitable for generator paralleling applications where reliable frequency and phase matching are required.
📋 Product Parameters & Datasheet
| Parameter | Specification |
|---|---|
| Brand | Woodward |
| Model | 9907-028 Rev F |
| Series | SPM-A |
| Product Name | Automatic Synchronizer |
| Place of Origin | USA (verify nameplate) |
| Product Status | Industrial synchronization control module |
| Dimensions | Approx. 315 × 210 × 44 mm |
| Weight | Approx. 2.2 kg |
| Rated Power | Maximum 5 W |
| Discontinued Status | Legacy product; verify current availability |
Additional Technical Specifications
- Input Voltage: 115 or 230 VAC RMS
- Operating Frequency: 50/60 Hz
- Voltage Tolerance: ±10%
- Phase Matching Window: ±10°
- Voltage Matching: Not included in 9907-028
- Power Consumption: 5 W maximum
- Operating Modes: RUN, CHECK, PERMISSIVE, OFF
- Breaker Close Relay: Normally open contact
- Match-Up Time: Selectable 1/8, 1/4, 1/2, or 1 second
- Maximum Operating Temperature: -45°C to +70°C
- Installation: Switchgear panel mounting
- Compatible Controls: Woodward 2301, 2301A, EPG, and 2500 series
Specifications are based on Woodward Manual 82384. The 9907-028 is the standard SPM-A version without automatic voltage matching.
🔧 Daily Maintenance & Care
1. Visual Inspection
Inspect the housing, mounting brackets, terminal blocks, and electrical connections for physical damage, corrosion, and overheating.
2. Electrical Connection Checks
Regularly examine bus voltage and generator voltage input wiring. Ensure that terminals are properly secured.
3. Voltage Monitoring
Check the voltage measurement signals and confirm that the connected potential transformers provide the correct input voltage.
4. Frequency and Phase Inspection
Monitor synchronization performance and verify that generator frequency and phase measurements remain stable.
5. Relay Maintenance
Inspect the breaker-close relay contacts for wear, oxidation, and abnormal switching behavior.
6. Cabinet Cleaning
Keep the control cabinet clean, dry, and adequately ventilated. Prevent dust and moisture from accumulating around the synchronizer.
7. Configuration Records
Maintain records of phase matching settings, operating modes, and governor compatibility parameters.
8. Functional Testing
Periodically test synchronization functions in accordance with the generator manufacturer’s maintenance procedures.
🛠️ Troubleshooting & Common Problems
1. Synchronizer Does Not Operate
- Check the AC voltage supply.
- Inspect bus and generator voltage connections.
- Verify the operating mode switch.
- Check internal fuses and wiring.
2. Generator Cannot Synchronize
- Check generator frequency and bus frequency.
- Inspect phase sequence and voltage measurement wiring.
- Verify the speed-bias output connection.
- Check governor response and synchronization settings.
3. Circuit Breaker Does Not Close
- Verify RUN mode selection.
- Inspect breaker-close relay wiring.
- Check external breaker interlocks.
- Confirm that synchronization conditions are satisfied.
4. Incorrect Phase Matching
- Check voltage transformer wiring.
- Inspect phase sequence and polarity.
- Verify phase-angle adjustment.
- Confirm that the selected matching window is correct.
5. Unstable Frequency Matching
- Inspect the governor speed-control system.
- Check the speed-bias signal.
- Review generator frequency fluctuations.
- Verify compatibility with the connected Woodward load-sharing controller.
6. Voltage Measurement Problems
- Check the 115/230 VAC input configuration.
- Inspect potential transformer connections.
- Verify that the input voltage remains within the specified tolerance.
⚠️ Safety Precautions
- Disconnect power before performing installation or maintenance.
- Only qualified electrical technicians should service the synchronizer.
- Verify voltage input configuration before connecting the device.
- Never bypass generator protection or breaker interlock circuits.
- Confirm phase sequence before attempting generator paralleling.
- Use appropriate protection when working with energized switchgear.
- Do not perform unauthorized adjustments to synchronization settings.
- Ensure that breaker-close circuits operate correctly before commissioning.
- Maintain independent generator overspeed and electrical protection systems.
⭐ Recommended Woodward Models – 15 Products
The following Woodward products are related to generator synchronization, speed control, load sharing, and power management.
| No. | Model | Product Name |
|---|---|---|
| 1 | 9907-029 | SPM-A Synchronizer with Voltage Matching |
| 2 | 9905-003 | SPM-A Synchronizer |
| 3 | 9905-004 | SPM-A Synchronizer |
| 4 | 9905-005 | SPM-A Synchronizer |
| 5 | 9905-006 | SPM-A Synchronizer |
| 6 | 9905-008 | SPM-A Synchronizer |
| 7 | 9905-009 | SPM-A Synchronizer |
| 8 | 9905-107 | SPM-A Synchronizer |
| 9 | 9905-797 | Digital Synchronizer and Load Control |
| 10 | 9905-131 | 2301A Speed Control |
| 11 | 9907-019 | 2301A Load Sharing and Speed Control |
| 12 | 9907-163 | 505 Digital Control |
| 13 | 8440-1884 | easYgen-2500-5 Genset Controller |
| 14 | 8440-2045 | easYgen-3400-5 Genset Controller |
| 15 | 8406-113 | EGCP-3 Generator Controller |
These models belong to related Woodward synchronization, governing, and generator-control product families. They are not all direct substitutes for the SPM-A 9907-028.
📌 Product Applications
- Diesel generator synchronization
- Gas generator paralleling
- Industrial power stations
- Marine generator control systems
- Standby power installations
- Multi-generator power management
- Generator breaker synchronization
- Industrial engine governor systems
Product Summary
The Woodward SPM-A 9907-028 Rev F is an automatic synchronizer designed to coordinate generator frequency and phase before parallel operation. Its compatibility with selected Woodward governor and load-sharing systems makes it a valuable component for industrial power generation and generator control applications.
Technical reference: Woodward SPM-A Synchronizer Installation and Operation Manual 82384. The 9907-028 is the 50/60 Hz, ±10° phase-angle version without voltage matching. The related 9907-029 provides 1% voltage matching.
Woodward+2