⚙️ Product Introduction
The Woodward 9905-096 Automatic Generator Loading Control is an industrial control device designed for generator load management and power generation applications.
It is intended to support automatic generator loading functions by coordinating generator operating conditions with load demand. In power generation systems, automatic loading control helps manage generator loading sequences and supports stable operation when electrical demand changes.
The 9905-096 is suitable for industrial generator installations, engine-driven power plants, marine power systems, and other applications requiring coordinated generator loading.
Its role in a generator control system is to help improve operating efficiency, support load management, and reduce the need for manual intervention during generator operation.
Typical applications include:
-
Industrial generator loading systems.
-
Standby and prime power installations.
-
Generator control and power management panels.
-
Marine electrical power systems.
-
Multi-generator power plants.
-
Industrial engine-driven generating equipment.
Before replacement or installation, verify the exact model number, wiring arrangement, control configuration, and compatibility with the existing generator system.
📋 Product Datasheet & Parameters
| Parameter | Specification |
|---|---|
| Brand | Woodward |
| Model | 9905-096 |
| Series | AGLC |
| Product Name | Automatic Generator Loading Control |
| Place of Origin | United States (manufacturer origin) |
| Product Status | Industrial generator control equipment |
| Dimensions | 8.5 × 7.5 × 2 inches (216 × 191 × 51 mm) |
| Weight | Approx. 2.25 lb (1.02 kg) |
| Rated Power / Input | 115/230 VAC, 50/60 Hz; 5 VA for 230 VAC version |
| Discontinued Status | Discontinued by manufacturer according to distributor listings |
Additional Technical Specifications
-
Input voltage, 115 VAC configuration: 88–132 VAC.
-
Input voltage, 230 VAC configuration: 170–264 VAC.
-
Maximum input current: 0.10 A.
-
Load ramp adjustment: 5 seconds to 5 minutes.
-
Unload ramp adjustment: 5 seconds to 5 minutes.
-
Load-sharing signal: 0–3 VDC.
-
Meter output: 0–1 mA.
-
Breaker relay contact rating: Up to 10 A at 28 VDC resistive.
-
Operating temperature: -40°C to +85°C.
-
Storage temperature: -55°C to +105°C.
-
Shock resistance: 60 G.
-
Enclosure: Metal chassis.
-
Certifications: UL and CSA Listed.
The power input is selectable between 115 VAC and 230 VAC. The correct terminal jumper configuration must be used for the selected supply.
🔧 Daily Maintenance & Care
1. Visual Inspection: Check the metal enclosure, terminal board, wiring, and front adjustment controls for damage or deterioration.
2. Power Supply Inspection: Verify that the AC supply is within the specified input range and remains stable during operation.
3. Terminal Maintenance: Inspect electrical connections for looseness, corrosion, and overheating.
4. Load Ramp Verification: Periodically check the loading and unloading ramp settings to ensure smooth generator load transitions.
5. Base Load Adjustment: Inspect the base-load reference and maximum load limit settings to prevent unintended generator overloading.
6. Relay Inspection: Check the breaker-open relay and auxiliary contacts for reliable switching.
7. Signal Inspection: Verify load-sharing signal connections and inspect shielded cables for damage or interference.
8. Environmental Maintenance: Keep the control cabinet clean, dry, and adequately ventilated.
9. Parameter Records: Maintain records of original adjustment settings and system configuration.
🛠️ Troubleshooting & Common Problems
1. Generator Does Not Load Automatically
-
Check the generator breaker auxiliary contacts.
-
Verify the AGLC power supply.
-
Inspect terminals 15 and 16.
-
Check the load-sharing signal connections.
-
Verify that the associated speed control is operating correctly.
2. Generator Loading Is Too Fast or Too Slow
-
Inspect the load ramp-time potentiometer.
-
Verify the unloading ramp adjustment.
-
Check the load-sharing signal.
-
Confirm that the selected ramp time matches the generator requirements.
3. Generator Fails to Unload
-
Check the unload switch connected to terminals 14 and 15.
-
Inspect the unload-trip-level setting.
-
Verify relay K1 operation.
-
Check the generator breaker opening circuit.
4. Base Load Cannot Be Maintained
-
Inspect the base-load reference setting.
-
Check the base-load limit adjustment.
-
Verify external potentiometer wiring.
-
Inspect the load-sharing control connections.
5. Generator Load Fluctuates
-
Check the load-sharing system.
-
Inspect shielded signal cables.
-
Verify that all AGLC units in the system are powered.
-
Check the associated speed controller operating mode.
6. Breaker Does Not Open During Unloading
-
Check relay K1.
-
Inspect terminals 18, 19, and 20.
-
Verify the breaker trip circuit.
-
Inspect auxiliary feedback contacts.
For suspected internal failures, Woodward’s installation manual recommends checking the surrounding control system and wiring before concluding that the AGLC itself is defective. Internal repair should be handled by qualified service personnel.
⚠️ Safety Precautions
-
Installation and maintenance must be performed by qualified electrical technicians.
-
Disconnect the AC supply before modifying wiring or terminal connections.
-
Confirm whether the unit is configured for 115 VAC or 230 VAC before energizing.
-
Use the correct terminal jumpers for the selected input voltage.
-
Never exceed the rated relay contact current.
-
Ensure all generator protection and emergency shutdown systems are operational.
-
Do not bypass breaker interlocks or generator protection circuits.
-
Use shielded wiring for sensitive control signals.
-
Observe electrostatic discharge precautions when handling internal electronic components.
-
Verify generator synchronization before connecting a generator to a live bus.
-
Keep independent overspeed protection active during commissioning and operation.
🔩 Recommended Woodward Models
The following 15 Woodward models are relevant to generator loading, speed regulation, synchronization, and power management applications.
| No. | Model | Product Description |
|---|---|---|
| 1 | 9905-063 | Automatic Generator Loading Control |
| 2 | 9905-089 | Process Import/Export Control |
| 3 | 9905-090 | Process Control |
| 4 | 9905-091 | Process Control |
| 5 | 9905-092 | Process Control |
| 6 | 9905-095 | TM40LP Control |
| 7 | 9905-107 | SPM-A Synchronizer |
| 8 | 9905-110 | 700 Series Digital Control |
| 9 | 9905-111 | 700 Series Digital Control |
| 10 | 9905-112 | 700 Series Digital Control |
| 11 | 9905-131 | 2301A Speed Control |
| 12 | 9905-132 | 2301A Load Sharing Control |
| 13 | 9905-144 | 2301A Control |
| 14 | 9905-145 | 2301A Control |
| 15 | 9905-150 | 2301A Control |
Recommended models are related Woodward control products, not direct replacements for 9905-096. Verify individual part numbers and configurations before purchasing.