The Honeywell TK-MDP081 is a high-performance Pulse Input Module designed for the Experion PKS (Process Knowledge System) Series C I/O family. This 8-channel module is specifically engineered to interface with field devices that generate pulse-train signals, such as flow meters, tachometers, and encoders. With the part number 51404351-175, it provides precise frequency and pulse counting capabilities, essential for accurate totalization and speed monitoring in industrial processes.
For availability and detailed ordering information, please visit our model catalog.
Product Specifications
| Feature | Details |
| Model Name | TK-MDP081 |
| Product ID | 51404351-175 |
| Series | Experion PKS Series C |
| Channel Count | 8 Isolated Channels |
| Input Frequency | 0.5 Hz to 50 kHz |
| Input Signal Level | 5V to 24V DC (Configurable) |
| Dimensions (WxHxD) | 165 x 121 x 45 mm |
| Net Weight | 0.45 kg |
| Coating | G3 Conformal Coating |
Operational Precautions
- Field Wiring Termination: Ensure that pulse signals are wired to the correct polarity on the associated IOTA (Input Output Termination Assembly). Reverse polarity can lead to missed counts or hardware errors.
- Signal Interference: Pulse inputs are highly sensitive to electrical noise. Use shielded twisted-pair cabling and ensure the shield is grounded only at the IOTA end to maintain signal integrity.
- Module Seating: When installing the module into the Series C rack, verify that the connector pins are straight. Applying excessive force to a misaligned module can damage the backplane of the IOTA.
- Configuration Limits: Verify the maximum input frequency in the Experion Control Builder. Exceeding the 50 kHz hardware limit will result in inaccurate pulse accumulation and potential buffer overflows.
FAQ (Questions & Answers)
Q: Can the TK-MDP081 be used for turbine flowmeter signals? A: Yes, it is commonly used to process raw pulse outputs from turbine flowmeters for high-accuracy liquid and gas flow totalization.
Q: Does this module support redundant configurations? A: Yes, the TK-MDP081 can be used in a redundant pair when mounted on a redundant Series C IOTA (such as the TK-TDP051) to ensure continuous monitoring.
Q: What is the significance of the -175 suffix? A: This suffix indicates the hardware revision and often confirms that the board has received G3 conformal coating, making it suitable for harsh or corrosive environments.
Similar Honeywell Series C Models
- TK-TDP011 (51308331-175): Digital Input Termination Assembly (Simplex).
- TK-PUIX01 (51404351-175): Alternative designation for the Pulse Input Module assembly.
- TK-FTEB01 (51309512-175): Fault Tolerant Ethernet Bridge module for C300 controllers.
- TK-IAH161 (51403479-175): 16-channel HART Analog Input Module.
- TK-ODA161 (51403476-175): 16-channel Digital Output Module (24V DC).