The ABB 07KT98-S H4 is a high-performance functional safety base unit belonging to the Advant Controller 31 (AC31) series. This “S” variant is specifically designed for safety-related applications, providing integrated logic for emergency shutdowns, interlocking, and critical process monitoring. The H4 designation typically indicates a specific hardware performance level and memory configuration, making it a cornerstone for decentralized automation in demanding industrial environments.
For availability and technical support on this model, please visit our specialized product page.
Product Specifications
| Feature | Details |
| Model Name | 07KT98-S H4 |
| Product ID | GJR5253100R2260 |
| Series | Advant Controller 31 (AC31) |
| Safety Class | Designed for SIL-rated applications |
| Onboard I/O | 24 Digital Inputs / 16 Digital Outputs (Relay/Transistor) |
| Analog I/O | 8 Analog Inputs / 4 Analog Outputs |
| Communication | CS31 System Bus, RS-232 Interface |
| Supply Voltage | 24V DC |
| Net Weight | 1.15 kg |
Operational Precautions
- Safety Loop Integrity: When using the 07KT98-S in a safety function, ensure that the peripheral sensors and actuators also meet the required Safety Integrity Level (SIL) to maintain the certification of the entire loop.
- Firmware Consistency: Use the correct version of the 907 AC 31 programming software. Incompatibility between the software library and the H4 hardware can lead to compilation errors or unpredictable logic behavior.
- CS31 Bus Termination: Always ensure that the CS31 system bus is correctly terminated with a 120-ohm resistor at the physical ends of the line to prevent data reflections and communication timeouts.
- Grounding Requirements: The metal DIN rail mounting must be bonded to a low-impedance functional earth to protect the sensitive internal safety logic from electromagnetic interference (EMI).
FAQ (Questions & Answers)
Q: What is the difference between the standard 07KT98 and the 07KT98-S? A: The “S” version is the safety-certified variant. It includes redundant internal self-tests and specialized hardware designed to fail into a “safe state” in the event of an internal component failure.
Q: Can the 07KT98-S H4 be expanded with additional I/O? A: Yes, it serves as a master unit that can control multiple decentralized I/O modules (such as the 07AC91 or 07AI91) via the integrated CS31 system bus.
Q: Is this unit compatible with the newer AC500 series? A: While they belong to different generations, ABB provides specific communication modules and gateways to allow AC31 systems to exchange data with modern AC500 PLCs.
Similar Advant Controller 31 Models
- 07KT94 (GJR5252100R0101): Standard base unit for non-safety-critical automation tasks.
- 07KT97 (GJR5253000R0160): Performance-oriented base unit with enhanced memory.
- 07KT98 (GJR5253100R0270): The non-safety version of the 07KT98 hardware.
- 07AC91 (GJR5252300R0101): Digital I/O expansion module for the CS31 bus.
- 07AI91 (GJR5252500R0101): Analog input expansion module for precise measurement.