Description
🔥 Product Introduction
The Honeywell IFP-75 is an intelligent addressable Fire Alarm Control Panel with an integrated communicator from the Farenhyt series. It combines fire detection, alarm processing, notification control, system supervision, and central-station communication in one compact control unit. Honeywell specifies the IFP-75 as a direct replacement for the IFP-50 family.
The panel includes one built-in SLC loop, two Flexput circuits, a dual-line digital alarm communicator/transmitter, IP communication capability, programmable relays, USB programming, and a four-line LCD display. It can also be networked with up to 32 panels/sites when the appropriate network interface is installed.
The IFP-75 is available in red, while the IFP-75B version uses a black cabinet. Honeywell currently identifies the IFP-75 product as discontinued, so replacement and surplus availability should be checked by exact model and suffix.
📋 Product Datasheet
| Parameter | Value |
|---|---|
| Brand | Honeywell |
| Model | IFP-75 |
| Series | Farenhyt Intelligent Fire Alarm Series |
| Product Name | Intelligent Fire Alarm Control Communicator |
| Country of Origin | USA |
| Product Status | Discontinued / Replacement & Surplus Availability |
| Dimensions | Approx. 12.71 × 15.12 × 3.33 in |
| Weight | Approx. 15 lb / 6.8 kg |
| Primary Power | 120 VAC 60 Hz or 240 VAC 50/60 Hz |
| SLC Capacity | Up to 75 IDP/SK detectors + 75 IDP/SK modules, or up to 75 SD devices |
The published specifications identify the IFP-75 as a single-SLC intelligent addressable panel. With IDP/SK devices, the maximum system point capacity is 150 points; with SD devices, the maximum is 75 points.
⚙️ Main Features
🔹 Built-in SLC signaling line circuit
🔹 Supports up to 75 IDP/SK detectors and 75 IDP/SK modules
🔹 Supports up to 75 SD SLC devices
🔹 Two Flexput circuits with up to 2.5 A maximum output capability
🔹 Built-in dual-line DACT
🔹 IP communication capability
🔹 Optional cellular communication
🔹 Four-line LCD display with 40 characters per line
🔹 Two programmable Form-C relays
🔹 One fixed Form-C trouble relay
🔹 Up to 125 software zones
🔹 Up to 125 output groups
🔹 Up to 16 SBUS devices
🔹 Supports up to four SWIFT wireless gateways
🔹 Each SWIFT gateway can support up to 49 wireless devices
🔹 USB interface for programming
🔹 JumpStart automatic programming
🔹 Field-upgradeable firmware
🔹 Network support for up to 32 sites
🔹 Surface or flush mounting capability
🔹 Built-in notification synchronization for compatible notification devices
🛠️ Operating Specifications & How to Use
⚠️ The IFP-75 is life-safety equipment. Installation, programming, testing, and commissioning should be performed by qualified fire-alarm personnel and according to the approved system design and applicable fire codes.
1. Installation
🔧 Mount the cabinet securely using the approved mounting arrangement.
🔧 Connect the incoming AC supply according to the applicable electrical requirements.
🔧 Connect the standby batteries with correct polarity.
🔧 Connect the SLC field wiring and verify the selected Class A or Class B configuration.
🔧 Connect notification appliances, auxiliary power, relays, annunciators, network interfaces, and communication equipment as required.
🔧 Inspect all field wiring for shorts, opens, grounding faults, and incorrect polarity before energizing the system.
2. Programming
💻 Connect the programming computer through the panel’s USB interface or use the approved programming method.
⚙️ Configure the SLC devices, zones, output groups, notification circuits, relays, communication settings, and system parameters.
🔎 Verify every programmed address against the actual field device.
📝 Save a backup of the final configuration for future maintenance.
The JumpStart function can assist with automatic system programming, while the USB interface provides a convenient method for configuration and service work.
3. Normal Operation
🟢 During normal operation, verify that the panel indicates a normal system condition.
🔎 The LCD should be checked periodically for alarm, supervisory, or trouble messages.
🔔 When an initiating device activates, the panel processes the event according to its programmed cause-and-effect logic.
📡 When communication is configured, alarm and trouble information can be transmitted to the designated monitoring station.
🔄 After the initiating condition has been corrected, an authorized operator can reset the system according to the approved operating procedure.
⚡ Power-Up Sequence
Follow the approved installation procedure rather than treating the IFP-75 as ordinary industrial equipment.
- 🔧 Complete all field wiring with power removed.
- 🔎 Inspect SLC, NAC, relay, communication, grounding, and battery wiring.
- 🔋 Verify the standby battery connection and polarity.
- ⚡ Apply the specified AC input.
- 🖥️ Allow the panel to complete its initialization.
- 🔎 Check the LCD and status indicators.
- ⚠️ Investigate any trouble, ground fault, battery fault, or communication fault.
- 🧪 Perform the required detector, notification, communication, and supervisory tests.
- ✅ Confirm that the system returns to normal monitoring status.
⛔ Power-Off / Shutdown Sequence
The fire alarm panel should normally remain powered continuously.
For authorized maintenance:
- 🚨 Notify the responsible facility personnel and monitoring station as required.
- 🔕 Place the system into the approved maintenance/test condition.
- ⚡ Disconnect the AC source according to the service procedure.
- 🔋 Disconnect the standby battery if complete power isolation is required.
- 🛠️ Perform the maintenance work.
- 🔋 Reconnect the battery correctly.
- ⚡ Restore AC power.
- 🖥️ Check the LCD and system indicators.
- 🧪 Perform the required functional tests.
- ✅ Return the system to normal operating condition.
Do not remove power simply to clear an alarm or trouble indication. The cause of the event should be identified and corrected first.
📖 Product Usage Instructions
The IFP-75 acts as the central controller for an intelligent addressable fire detection system.
The SLC connects compatible addressable detectors and modules. The panel evaluates device status and generates programmed alarm, supervisory, or trouble events.
The two Flexput circuits can be configured for notification outputs or auxiliary power. Available auxiliary-power functions include door-holder, constant, resettable, and sounder-synchronization applications.
The built-in communicator can transmit system information to a central station using supported communication methods. IP communication can be used alongside telephone-line communication, while optional cellular communication can provide another reporting path.
For networked installations, the appropriate network interface allows multiple panels to operate as a larger system, with Honeywell specifying support for up to 32 panels/sites. Copper and fiber network configurations are supported with the corresponding interface equipment.
❓ Common Questions & Answers
Q1: What is the Honeywell IFP-75?
A: It is an intelligent addressable fire alarm control panel with an integrated communicator, designed for fire detection, alarm notification, supervision, and central-station reporting.
Q2: Is the IFP-75 the same as the IFP-75B?
A: The basic control-panel platform is the same, but the cabinet versions differ. The IFP-75 is offered in red, while the IFP-75B is the black-cabinet version.
Q3: How many addressable devices can it support?
A: The published specification supports up to 75 IDP/SK detectors and 75 IDP/SK modules, giving a maximum of 150 IDP/SK points. With SD devices, the maximum is 75 points.
Q4: Does the IFP-75 have an LCD display?
A: Yes. The panel has a four-line LCD display with 40 characters per line.
Q5: Does it have built-in communication?
A: Yes. The IFP-75 includes a dual-line DACT with IP communication capability, with optional cellular communication available depending on the configuration.
Q6: Can the IFP-75 be networked?
A: Yes. The system can support networking of up to 32 panels/sites using the appropriate network interface hardware.
Q7: Can the IFP-75 be used with wireless devices?
A: Yes. The system supports SWIFT wireless gateways. Up to four gateways can be supported, with each gateway supporting up to 49 wireless devices.
Q8: Does the IFP-75 support USB programming?
A: Yes. A built-in USB interface is provided for programming and service operations.
Q9: Is the IFP-75 still a current product?
A: Honeywell currently identifies the IFP-75 product as discontinued. Existing equipment and replacement stock may still be available, so the exact model and condition should be verified before purchase.
Q10: Can an IFP-75 replacement be installed without checking the existing configuration?
A: No. The SLC device type, firmware, programming database, notification circuits, communication configuration, network arrangement, and system approvals should all be checked before replacement.
🔧 Recommended Honeywell Related Models
- Honeywell IFP-75B — Black-Cabinet Intelligent Fire Alarm Control Panel
- Honeywell IFP-75HV — High-Voltage Intelligent Fire Alarm Control Panel
- Honeywell IFP-75HVB — High-Voltage Black-Cabinet Version
- Honeywell IFP-50 — Previous-Generation Intelligent Fire Alarm Control Panel
- Honeywell IFP-2100 — Intelligent Addressable Fire Alarm Control Panel
- Honeywell IFP-2100ECS — Fire Alarm Control Panel with Emergency Communication System
- Honeywell RFP-2100 — Remote Fire Alarm Panel
- Honeywell RA-100 — Remote LCD Annunciator
- Honeywell RA-1000 — Remote LCD Annunciator
- Honeywell RA-2000 — Remote LCD Annunciator
These models and accessories belong to related Honeywell/Farenhyt fire-alarm product families and can be relevant when replacing or expanding an existing IFP-based installation.
★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★
One year warranty, special discount after sale
The company focuses on DCS, PLC, robot, large servo four systems
The main products are all kinds of module/card, controller, touch screen, servo drive
The company's advantages: the supply of imported original products, professional production of accessories
Fast delivery time, complete supply, The seller has more than $1526000 worth of industrial control products inventory
We Can transport to the world!!!
——————————————————————————————————————
[service contact information]
Purchase and consultation hotline: +8613365909307 (Whatsapp/ Wechat)
E-mail: dcsplcsales@gmail.com
Contact Person: Simon
① 24-hour email reply (12 hours);
② For shipment to countries outside Asia, please contact the seller.
Main brands include: ABB, Bailey, GE, FOXBORO, Invensys TRICONEX, Bentley BENTLY, A-B Rockwell, EMERSON EMERSON, B&R, MOTOROLA, FUANC, REXROTH, KUKA, HONEYWELL, NI, DEIF, Yokogawa, WOODWARD WOODWARD, Ryan, SCHNEIDER SCHNEIDER, Yaskawa, MOOG, EPRO, PROSOFT and other major brands
Related Products: