The YOKOGAWA AAI143-S00 is a 16-channel isolated analog input module for Yokogawa FIO-based distributed control systems. It accepts standard 4–20 mA current signals from industrial transmitters and converts the field signals into data for process monitoring and control. Yokogawa’s official specification identifies the AAI143 as a 16-channel, isolated 4–20 mA analog input module.
The -S00 designation corresponds to the standard/basic version. The module supports both 2-wire and 4-wire transmitter configurations through channel-level setting pins and can provide transmitter power within its specified operating range.
🔹 Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | YOKOGAWA |
| Model | AAI143-S00 |
| Series | FIO Analog I/O |
| Product Name | 16-Channel Isolated Analog Input Module |
| Input Channels | 16 |
| Input Signal | 4–20 mA DC |
| Allowable Input Current | 24 mA |
| Isolation Withstand Voltage | 1500 V AC, 1 minute |
| Accuracy | ±16 µA |
| Data Update Period | 10 ms |
| Transmitter Power Supply | 19.0–25.5 V DC, application dependent |
| Maximum Current Consumption | 230 mA at 5 V DC / 540 mA at 24 V DC |
| Dimensions | Approx. 107.5 × 32.8 × 130 mm |
| Weight | Approx. 0.3 kg |
| Country of Origin | Japan |
The core specifications above are consistent with Yokogawa’s published AAI143 documentation, including 16 isolated inputs, 4–20 mA input, 24 mA allowable input current, 1500 V AC isolation withstand voltage, ±16 µA accuracy and 10 ms data update period.
🔹 Main Features
📡 16 Isolated Analog Inputs
The module provides 16 isolated channels for collecting 4–20 mA process signals.
⚙️ 4–20 mA Signal Input
It is designed for standard industrial current transmitters used for pressure, flow, level, temperature and other process measurements.
🔌 2-Wire / 4-Wire Transmitter Support
The transmitter configuration can be selected individually for each channel using the appropriate setting pin.
⚡ Transmitter Power Supply
The module can supply compatible transmitters, with the specification indicating at least 19.0 V at 20 mA and a maximum of 25.5 V at 0 mA, with a 25 mA output-current limit.
🛡️ High Electrical Isolation
Input-to-system withstand voltage is specified at 1500 V AC for one minute.
🔄 Fast Data Updating
The specified data update period is 10 ms, making the module suitable for continuously monitored process variables.
🔹 Operating Procedure — How to Use
- 🔍 Confirm the module marking AAI143-S00 before installation.
- 🧩 Confirm that the host system and FIO configuration support the AAI143 module.
- 📋 Check the transmitter type for every channel.
- 🔧 Set each channel for the required 2-wire or 4-wire transmitter arrangement.
- 🔌 Connect the 4–20 mA field wiring to the correct terminals.
- ⚡ Verify transmitter supply requirements before applying power.
- 🖥️ Configure the corresponding input channels in the Yokogawa control-system engineering environment.
- ⚡ Power up the system.
- 📊 Confirm that each channel receives a reasonable process value.
- 🧪 Perform a loop test using the actual transmitter or an approved 4–20 mA signal source.
- 🚨 Check for open-loop, abnormal-current or communication diagnostics.
- ✅ Return the loop to normal automatic control after all channels have passed testing.
🔹 Power-Up Sequence
⚠️ The exact sequence should follow the Yokogawa system and plant maintenance procedure.
- 🔒 Place the process in an approved maintenance condition.
- ⚡ Confirm field wiring is complete.
- 🔌 Check polarity and terminal connections.
- 🧩 Confirm the AAI143-S00 is correctly installed.
- 📡 Verify the FIO communication/interface connection.
- ⚡ Apply system power.
- 💡 Check module/system diagnostic indications.
- 🖥️ Confirm the module is recognized by the control system.
- 📈 Check all 16 analog input channels.
- 🔧 Verify transmitter values against local instruments.
- 🚨 Clear or investigate abnormal diagnostics.
- ✅ Return the system to normal operation.
🔹 Shutdown Sequence
- 🛑 Place the process/control loop in the approved shutdown state.
- 📊 Record current input values and diagnostics.
- 🔒 Put the system into maintenance condition.
- ⚡ Isolate the appropriate field and system power.
- 🔌 Confirm the circuit is electrically safe.
- 🧤 Use ESD protection when handling the module.
- 🔧 Disconnect field wiring only after isolation is confirmed.
- 🧩 Remove or replace the module as required.
🔹 Product Usage
The AAI143-S00 is intended for process signal acquisition in Yokogawa DCS/FIO architectures.
Typical applications include:
🏭 Process automation
🛢️ Oil and gas facilities
⚗️ Chemical and petrochemical plants
⚡ Power generation
💧 Water and wastewater treatment
🌡️ Temperature monitoring
💨 Pressure measurement
🌊 Flow measurement
📏 Level measurement
🏗️ General industrial process control
The module is particularly suitable when multiple isolated 4–20 mA field transmitters need to be connected to a Yokogawa control system.
🔹 Wiring & Configuration Notes
🔌 4–20 mA Wiring
The AAI143 supports both 2-wire transmitter input and 4-wire current-input arrangements. Yokogawa documentation specifies different terminal connections for these configurations.
⚙️ Channel Setting
The 2-wire/4-wire configuration is set individually by channel. Do not assume all 16 channels must use the same transmitter type.
⚡ Power-Off Condition
Yokogawa documentation notes that when the AAI143 is powered off or abnormal, the current-input loop becomes open. Therefore, an external receiving device should not simply be connected to the same current loop without following the specified wiring arrangement.
🛡️ Terminal Selection
Depending on the installation, Yokogawa provides compatible terminal options such as pressure-clamp terminals, dual-pressure terminals and terminals with surge absorption.
🔹 Common Questions & Answers
Q1: What is YOKOGAWA AAI143-S00?
A: It is a 16-channel isolated analog input module designed for 4–20 mA signals in Yokogawa FIO systems.
Q2: How many channels does it have?
A: It has 16 isolated analog input channels.
Q3: What signal does it accept?
A: The standard input signal is 4–20 mA DC.
Q4: Can it connect to 2-wire transmitters?
A: Yes. The module supports 2-wire transmitter configurations and can provide transmitter power within its specified limits.
Q5: Can it be used with 4-wire transmitters?
A: Yes. The input configuration can be set for 4-wire transmitter/current-input applications.
Q6: Is AAI143-S00 an analog output module?
A: No. AAI143 is an analog input module. The corresponding Yokogawa 4–20 mA analog output module is the AAI543.
Q7: Does AAI143-S00 support HART?
A: The basic AAI143-S00 is the standard/basic version. Yokogawa separately identifies the -H suffix as the version with HART digital communication.
Q8: What is the accuracy?
A: The specified accuracy is ±16 µA.
Q9: What is the data update period?
A: The specified data update period is 10 ms.
Q10: What is the weight?
A: Approximately 0.3 kg.
🔹 Recommended YOKOGAWA Models / Series
- YOKOGAWA AAI141 | Analog Input Module
- YOKOGAWA AAI143 | 16-Channel Isolated 4–20 mA Analog Input
- YOKOGAWA AAI143-H | 16-Channel Analog Input with HART
- YOKOGAWA AAI543 | 16-Channel Isolated Analog Output
- YOKOGAWA AAV144 | 16-Channel Isolated Analog Input, Voltage
- YOKOGAWA AAV544 | 16-Channel Isolated Analog Output, Voltage
- YOKOGAWA AAT141 | Thermocouple / mV Input Module
- YOKOGAWA AAR145 | RTD / Resistance Input Module
- YOKOGAWA AAI135 | Analog Input Module
- YOKOGAWA AAI835 | Analog Input Module
Yokogawa’s official FIO documentation lists AAI143 alongside AAI141, AAI543, AAV144, AAV544, AAT141 and other analog I/O modules in the same product architecture.
★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★
One year warranty, special discount after sale
The company focuses on DCS, PLC, robot, large servo four systems
The main products are all kinds of module/card, controller, touch screen, servo drive
The company's advantages: the supply of imported original products, professional production of accessories
Fast delivery time, complete supply, The seller has more than $1526000 worth of industrial control products inventory
We Can transport to the world!!!
——————————————————————————————————————
[service contact information]
Purchase and consultation hotline: +8613365909307 (Whatsapp/ Wechat)
E-mail: dcsplcsales@gmail.com
Contact Person: Simon
① 24-hour email reply (12 hours);
② For shipment to countries outside Asia, please contact the seller.
Main brands include: ABB, Bailey, GE, FOXBORO, Invensys TRICONEX, Bentley BENTLY, A-B Rockwell, EMERSON EMERSON, B&R, MOTOROLA, FUANC, REXROTH, KUKA, HONEYWELL, NI, DEIF, Yokogawa, WOODWARD WOODWARD, Ryan, SCHNEIDER SCHNEIDER, Yaskawa, MOOG, EPRO, PROSOFT and other major brands
Related Products: