Description
The YOKOGAWA PW482-10 is a 220–240 VAC input power supply module used in Yokogawa CENTUM control-system infrastructure. It can be installed in Field Control Units (FCUs), FIO Node Units, and Optical ESB Bus Repeater Units. Two identical PW482 modules can be installed for a dual-redundant power configuration.
The module is designed specifically for Yokogawa system hardware and should not be treated as a general-purpose AC/DC power supply. Yokogawa’s own specification states that the output voltage and current are not specified as generic power-supply ratings because the PW482 is intended exclusively for compatible FCU, FIO Node Unit, and Optical ESB Bus Repeater applications.
📋 Product Datasheet
| Parameter | Specification |
|---|---|
| Brand | YOKOGAWA |
| Model | PW482-10 |
| Series | PW482 |
| Product Name | AC Input Power Supply Module |
| Application | CENTUM / FIO Process Control System |
| Input Voltage | 220–240 VAC ±10% |
| Frequency | 50/60 Hz ±3 Hz |
| Maximum Power Consumption | 230 VA |
| Input Current | Approx. 1.3 A |
| Input Interface | Dedicated Connector |
| Redundancy | Dual-Redundant Configuration Supported |
| Installation Units | FCU / FIO Node Unit / Optical ESB Bus Repeater Unit |
| Weight | Approx. 1 kg |
| Dimensions | Approx. 49.7 × 146.5 × 190 mm |
| Product Status | Legacy / Discontinued |
| Country of Origin | Japan |
The official Yokogawa specification confirms 220–240 VAC ±10%, 50/60 Hz ±3 Hz, maximum power consumption of 230 VA, approximately 1 kg weight, and dedicated input/output connectors.
⚠️ Output note: Do not use generic 5.1 VDC/24 VDC output figures from third-party listings as a universal specification for every PW482-10 configuration. Yokogawa explicitly states that the output voltage/current are not specified as generic power-supply ratings because the module is dedicated to its intended Yokogawa system units.
⚙️ Main Functions
🔹 Provides operating power for compatible Yokogawa control-system hardware.
🔹 Supports Field Control Unit power requirements.
🔹 Supports FIO Node Unit applications.
🔹 Supports Optical ESB Bus Repeater Unit applications.
🔹 Allows dual-redundant power configuration when two identical modules are installed.
🔹 Provides an AC input interface for 220–240 VAC plant power.
🔹 Supports continuous operation in industrial process-control environments.
🛠️ Operating Instructions & How to Use
- 🔍 Confirm the installed system uses a compatible Yokogawa FCU, FIO Node Unit, or Optical ESB Bus Repeater Unit.
- 🏷️ Verify the complete module marking PW482-10.
- ⚡ Confirm that the incoming supply is 220–240 VAC.
- 📏 Verify that the input frequency is 50/60 Hz.
- 🔌 Inspect the dedicated connector and wiring.
- 🧰 Confirm that the module is installed in the correct power-supply position.
- 🔧 Make sure the module is firmly seated.
- ⚡ Apply AC power according to the system commissioning procedure.
- 🟢 Check the FCU/FIO system status.
- 📊 Verify that the associated I/O and communication modules initialize correctly.
- 🔄 For redundant systems, confirm that both power-supply modules are recognized correctly.
- ✅ Return the process-control system to normal operation after all diagnostics are clear.
Yokogawa documentation specifies that PW481/PW482/PW484 power modules are installed in the designated power-supply slots, with P1 used for a single configuration and two identical modules used for dual redundancy.
🔌 Power-On Sequence
For a Yokogawa control-system cabinet, use the following general sequence:
- 🧰 Confirm all modules are properly installed.
- 🔌 Check AC input wiring.
- ⚡ Measure the incoming voltage before energization.
- 🔍 Confirm the voltage is within the 220–240 VAC ±10% range.
- 🛡️ Verify protective grounding and upstream protection.
- ⚡ Energize the power supply.
- ⏳ Allow the PW482-10 and system modules to initialize.
- 🖥️ Check system diagnostic information.
- 📡 Confirm communication with the control system.
- 🔍 Check FIO and FCU status.
- 🔄 If redundant, verify the standby power module is available.
- ✅ Start normal process operation.
🔻 Power-Off / Shutdown Sequence
- 🛑 Place the controlled process into a safe condition.
- 🖥️ Stop automatic control according to the plant procedure.
- 💾 Save required system information and maintenance records.
- ⚡ Switch off the associated AC power source.
- 🔒 Apply lockout/tagout procedures where required.
- ⏳ Wait for internal circuits to discharge.
- 🔍 Verify that hazardous voltage is absent.
- 🔧 Remove the PW482-10 only after electrical isolation is confirmed.
- 📦 Place the removed module in antistatic protective packaging.
- 🔄 After replacement, verify wiring and module seating before restoring power.
📖 Product Usage Notes
The PW482-10 is a system-specific power module, not an independent industrial AC/DC supply.
A typical application can be represented as:
220–240 VAC Supply → PW482-10 → Yokogawa FCU / FIO Node / Optical ESB Repeater → Control & I/O Modules
The module can be used in a redundant arrangement:
PW482-10 #1 + PW482-10 #2 → Dual-Redundant System Power
Yokogawa specifies that two identical power-supply modules are required for a dual-redundant configuration.
🔍 Compatible Installation Units
The PW482 family can be installed in:
🔹 FCU: AFV30D / AFV30S
🔹 FCU: A2FV50D / A2FV50S
🔹 FCU: A2FV70D / A2FV70S
🔹 FIO Node Unit: ANB10D / ANB10S
🔹 FIO Node Unit: ANB11D / ANB11S
🔹 Optical ESB Bus Repeater Unit: ANT10U
🔹 Base Plate: A2BE1D / A2BE2D
These installation references are documented for the PW481/PW482/PW484 family.
🧪 Inspection Before Installation
🔍 Check the model label.
🔍 Confirm PW482-10.
🔍 Inspect the enclosure for cracks or deformation.
🔍 Check the dedicated connector.
🔍 Inspect terminals and contacts for oxidation.
🔍 Check for overheating marks.
🔍 Look for corrosion or moisture.
🔍 Confirm the AC input voltage.
🔍 Check the mounting position.
🔍 Verify the associated FCU/FIO unit.
🔍 For redundant systems, confirm that the second module has the same model configuration.
⚠️ Important Replacement Notes
When replacing a PW482-10, do not select a module only because the housing looks similar.
Pay particular attention to:
🔹 PW481 vs. PW482 vs. PW484
🔹 Input voltage
🔹 Complete suffix code
🔹 System unit type
🔹 Connector configuration
🔹 Single vs. redundant installation
🔹 Hardware revision
🔹 Existing system configuration
The basic PW48 family differentiates primarily by input power: PW481 = 100–120 VAC, PW482 = 220–240 VAC, and PW484 = 24 VDC.
❓ Common Questions & Answers
Q: What is YOKOGAWA PW482-10?
A: It is a 220–240 VAC input power supply module for compatible Yokogawa process-control system hardware.
Q: What voltage does PW482-10 use?
A: It uses 220–240 VAC ±10% at 50/60 Hz ±3 Hz.
Q: What is the maximum power consumption?
A: The specified maximum power consumption is 230 VA.
Q: What is the weight?
A: Yokogawa specifies approximately 1 kg.
Q: Can PW482-10 be used as a standalone power supply?
A: No. Yokogawa specifically states that the PW48 series is an exclusive module for FCU, FIO Node Unit, and Optical ESB Bus Repeater Unit applications.
Q: Can two PW482-10 modules be used together?
A: Yes. Two identical modules can be used for a dual-redundant power configuration.
Q: What is the difference between PW481 and PW482?
A: PW481 is designed for 100–120 VAC input, while PW482 is designed for 220–240 VAC input.
Q: What is the difference between PW482 and PW484?
A: PW482 uses 220–240 VAC input, while PW484 uses 24 VDC input.
Q: Can PW482 replace PW484?
A: No. Their input power types are different. The complete system configuration must be checked before replacement.
Q: Does the PW482-10 have a generic DC output rating?
A: Yokogawa’s official specification does not define the output as a generic power-supply rating because the module is designed specifically for its associated Yokogawa system units.
Q: What should I check before purchasing?
A: Check the exact model, suffix, input voltage, connector arrangement, installation unit, hardware revision, and whether the system uses redundant power supplies.
⭐ Recommended YOKOGAWA Models / Series
- YOKOGAWA PW481 — 100–120 VAC Input Power Supply Module
- YOKOGAWA PW482 — 220–240 VAC Input Power Supply Module
- YOKOGAWA PW484 — 24 VDC Input Power Supply Module
- YOKOGAWA PW482-10 S2 — PW482 Power Supply Variant
- YOKOGAWA PW481-10 — PW481 Power Supply Variant
- YOKOGAWA PW484-10 — PW484 Power Supply Variant
- YOKOGAWA PW482-11 — Related PW482 Configuration
- YOKOGAWA PW482-12 — Related PW482 Configuration
- YOKOGAWA PW484-11 — Related PW484 Configuration
- YOKOGAWA PW484-12 — Related PW484 Configuration
📦 Storage & Handling
📦 Store the module in a clean, dry environment.
🛡️ Use ESD-safe packaging for long-term storage and transportation.
💧 Protect the module from condensation and moisture.
🔌 Protect the dedicated connector from impact and contamination.
🌡️ Avoid excessive heat and direct sunlight.
🏷️ Keep the original model label and revision information intact.
Before installation, compare the replacement module against the original PW482-10 and confirm that the input voltage and system application are identical.
Recommended Short Listing Title
YOKOGAWA PW482-10 | AC Input Power Supply Module | 220-240VAC
★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★★
One year warranty, special discount after sale
The company focuses on DCS, PLC, robot, large servo four systems
The main products are all kinds of module/card, controller, touch screen, servo drive
The company's advantages: the supply of imported original products, professional production of accessories
Fast delivery time, complete supply, The seller has more than $1526000 worth of industrial control products inventory
We Can transport to the world!!!
——————————————————————————————————————
[service contact information]
Purchase and consultation hotline: +8613365909307 (Whatsapp/ Wechat)
E-mail: dcsplcsales@gmail.com
Contact Person: Simon
① 24-hour email reply (12 hours);
② For shipment to countries outside Asia, please contact the seller.
Main brands include: ABB, Bailey, GE, FOXBORO, Invensys TRICONEX, Bentley BENTLY, A-B Rockwell, EMERSON EMERSON, B&R, MOTOROLA, FUANC, REXROTH, KUKA, HONEYWELL, NI, DEIF, Yokogawa, WOODWARD WOODWARD, Ryan, SCHNEIDER SCHNEIDER, Yaskawa, MOOG, EPRO, PROSOFT and other major brands
Related Products: